What is the source of my water?
The sources of drinking water (both tap water and bottled water) include rivers, lakes, streams, ponds, reservoirs, springs, and groundwater wells. As water travels over the surface of the land or through the ground, it dissolves naturally-occurring minerals and, in some cases, radioactive material, and can pickup substances resulting from the presence of animals or from human activity.
Our water comes from the following source(s):

Source Name

Type

CC 1 MACON CO. #1MO2024363

Surface Water

Our drinking water is supplied from another water system through a Consecutive Connection (CC). To find out more about our drinking water sources and additional chemical sampling results, please contact our office at the number provided below.
Why are there contaminants in my water?
Drinking water, including bottled water, may reasonably be expected to contain at least small amounts of some contaminants. The presence of contaminants does not necessarily indicate that water poses a health risk. More information about contaminants and potential health effects can be obtained by calling the Environmental Protection Agency’s Safe Drinking Water Hotline (800-426-4791).
Contaminants that may be present in source water include:
A. Microbial contaminants, such as viruses and bacteria, which may come from sewage treatment plants, septic systems, agricultural livestock operations, and wildlife.
B. Inorganic contaminants, such as salts and metals, which can be naturally-occurring or result from urban stormwater runoff, industrial, or domestic wastewater discharges, oil and gas production, mining, or farming.
C. Pesticides and herbicides, which may come from a variety of sources such as agriculture, urban stormwater runoff, and residential uses.
D. Organic chemical contaminants, including synthetic and volatile organic chemicals, which are by-products of industrial processes and petroleum production, and can also come from gas stations, urban stormwater runoff, and septic systems.
E. Radioactive contaminants, which can be naturally-occurring or be the result of oil and gas production and mining activities.
In order to ensure that tap water is safe to drink, the Department of Natural Resources prescribes regulations which limit the amount of certain contaminants in water provided by public water systems. Department of Health regulations establish limits for contaminants in bottled water which must provide the same protection for public health.
Is our water system meeting other rules that govern our operations?
The Missouri Department of Natural Resources regulates our water system and requires us to test our water on a regular basis to ensure it's safety. Our system has been assigned the identification number MO2010165 for the purposes of tracking our test results. Last year, we tested for a variety of contaminants. The detectable results of these tests are on the following pages of this report. Any violations of state requirements or standards will be further explained later in this report.
How might I become actively involved?
If you would like to observe the decision-making process that affect drinking water quality or if you have any further questions about your drinking water report, please call us at 660-699-2270 to inquire about scheduled meetings or contact persons.
Do I need to take any special precautions?
Some people may be more vulnerable to contaminants in drinking water than the general population. Immuno-compromised persons such as persons with cancer undergoing chemotherapy, persons who have undergone organ trans-plants, people with HIV/AIDS or other immune system disorders, some elderly, and infants can be particularly at risk from infections. These people should seek advice about drinking water from their health care providers. EPA/CDC guidelines on appropriate means to lessen the risk of infection by Cryptosporidium and other microbial contaminants are available from the Safe Drinking Water Hotline (800-426-4791).

Contaminants Report
Definitions:
MCLG: Maximum Contaminant Level Goal, or the level of a contaminant in drinking water below which there is no known or expected risk to health. MCLGs allow for a margin of safety.
MCL: Maximum Contaminant Level, or the highest level of a contaminant that is allowed in drinking water. MCLs are set as close to the MCLGs as feasible using the best available treatment technology.
AL: Action Level, or the concentration of a contaminant which, when exceeded, triggers treatment or other requirements which a water system must follow..
TT: Treatment Technique, or a required process intended to reduce the level of a contaminant in drinking water.
90th percentile: For lead and Copper testing. 10% of test results are above this level and 90% are below this level.
Level Found: is the average of all test results for a particular contaminant.
Range of Detections: Shows the lowest and highest levels found during a testing period, if only one sample was taken, then this number equals the Level Found.
MRLDG: Maximum Residual Disinfectant Level Goal, or the level of a drinking water disinfectant below which there is no known or expected risk to health.
MRDL: Maximum Residual Disinfectant Level, or the highest level of a disinfectant allowed in drinking water.
Abbreviations:
PPB: parts per billion or micrograms per liter.
ppm: parts per million or milligrams per liter.
n/a: not applicable.
NTU: Nephelometric Turbidity Unit, used to measure cloudiness in drinking water.
MFL: million fibers per liter, used to measure asbestos concentration.
nd: not detectable at testing limits.
The state has reduced monitoring requirements for certain contaminants to less often than once per year because the concentrations of these contaminants are not expected to vary significantly from year to year. Records with a sample year more than one year old are still considered representative.

Regulated Contaminants

Disinfection By Products

Monitoring Period

RAA

Range

Unit

MCL

MCLG

Typical Source

No Detected Results were Found in the Calendar Year of 2007

Lead and Copper

Date

90TH Percentile

Range

Unit

AL

Sites
Over AL

Typical Source

COPPER

2005 - 2007

0.0479

0.0151 - 0.0632

ppm

1.3

0

Corrosion of household plumbing systems

LEAD

2005 - 2007

1.5

1.11 - 2.53

ppb

15

0

Corrosion of household plumbing systems

Microbiological

Result

MCL

MCLG

Typical Source

No Detected Results were Found in the Calendar Year of 2007

Violations and Health Effects Information

During the 2007 calendar year, we had the below noted violation(s) of drinking water regulations.

Type

Category

Analyte

Compliance Period

No Violations Occurred in the Calendar Year of 2007

Any Additional Required Health Effects Language or Violation Notices
There are no additional required health effects notices.
There are no additional required health effects violation notices.

Reseller Contaminants


Regulated Contaminants

Collection Date

Water
System

Highest Value

Range

Unit

MCL

MCLG

Typical Source

ATRAZINE

5/21/2007

CLARENCE CANNON WHOLESALE WTR COMM

0.67

0.67

ppb

3

3

Runoff from herbicide used on row crops

BARIUM

11/6/2007

UNIONVILLE

0.0726

0.0726

ppm

2

2

Discharge of drilling wastes; Discharge from metal refineries; Erosion of natural deposits

FLUORIDE

9/10/2007

KIRKSVILLE

1.41

0.76 - 1.41

ppm

4.0

4

Natural deposits; Water additive which promotes strong teeth.

NITRATE+
NITRITE
(AS N)

6/18/2007

CLARENCE CANNON WHOLESALE WTR COMM

1.5

1.5

ppm

10

10

Runoff from fertilizer use; Leaching from septic tanks, sewage; Erosion of natural deposits

Secondary Contaminants

Collection Date

Water
System

Highest Value

Range

Unit

MCL

MCLG

Typical Source

ALKALINITY, CACO3 STABILITY

11/6/2007

UNIONVILLE

138

138

MG/L

ALKALINITY, TOTAL

2/12/2007

UNIONVILLE

124

93 - 124

MG/L

ALUMINUM

9/17/2007

KIRKSVILLE

0.238

0.238

MG/L

0.05

CALCIUM

11/5/2007

CLARENCE CANNON WHOLESALE WTR COMM

57.9

57.9

MG/L

CARBON, TOTAL ORGANIC (TOC)

5/17/2007

CLARENCE CANNON WHOLESALE WTR COMM

10.1

2.68 - 10.1

ppm

Naturally present in the environment

CHLORIDE

11/5/2007

CLARENCE CANNON WHOLESALE WTR COMM

49.1

49.1

MG/L

250

CHLORITE

2/12/2007

MACON

0.46

0.07 - 0.46

ppm

1.0

0.8

By-product of drinking water chlorination

HARDNESS, CARBONATE

11/5/2007

CLARENCE CANNON WHOLESALE WTR COMM

168

168

MG/L

IRON

11/5/2007

CLARENCE CANNON WHOLESALE WTR COMM

0.00505

0.00505

MG/L

0.3

MAGNESIUM

9/17/2007

KIRKSVILLE

7.15

7.15

MG/L

MANGANESE

10/16/2007

MACON

0.00418

0.00418

MG/L

0.05

PH

10/16/2007

MACON

7.87

7.87

PH

8.5

POTASSIUM

11/5/2007

CLARENCE CANNON WHOLESALE WTR COMM

6.95

6.95

MG/L

SODIUM

11/5/2007

CLARENCE CANNON WHOLESALE WTR COMM

16.5

16.5

MG/L

20

SOLIDS, TOTAL DISSOLVED (TDS)

9/17/2007

KIRKSVILLE

337

337

MG/L

500

SULFATE

11/6/2007

UNIONVILLE

55.1

55.1

MG/L

250

During the 2007 calendar year, the water system(s) that we purchase water from had the below noted violation(s) of drinking water regulations.

Water System

Type

Category

Analyte

Compliance Period

No Violations Occurred in the Calendar Year of 2007